This opportunity invites qualified subcontractors to design, manufacture, supply, deliver, test, and commission four complete uninterruptible power supply (UPS) systems rated at 210 kVA, 400V with redundant N+1 architecture across three sites: Stoneleigh (1 unit), Canley Brook (1 unit), and Burton Green (2 units). Each UPS must feature four 60 kW hot-swappable power modules, complete VRLA battery systems with 90-minute autonomy, isolation transformers (250 kVA, 1:1 Dzn0), automatic transfer switches, static switching equipment, and building management system interfaces. The scope includes all interconnecting cables, protective devices, terminations, factory acceptance testing, site commissioning, and load bank validation to demonstrate redundancy, transfer operation, and fault-current performance (987 A for 200 ms). Specific site requirements vary: Stoneleigh requires 35 kW battery sizing with 31 kW connected load; Canley Brook requires 17 kW battery sizing with design load to be confirmed; Burton Green requires 70 kW battery sizing with 66 kW connected load per unit. Equipment must fit within standard cabinet dimensions of 1,200W x 1,996H x 1,100D mm. Suppliers must submit comprehensive equipment drawings, schematics, protection data, test results, commissioning records, and operation and maintenance manuals, and confirm any deviations from specifications before manufacture.